Heat recovery in schools

MKW 1500 Heat recovery for schools 500–1500 m³/h

Heat recovery in schools MKW 1500

Compact heat recovery unit with integrated supply air system for schools, small and medium-sized industrial facilities, and large laboratories


The role of plastic heat exchangers:

Due to the implementation of current thermal insulation regulations for buildings, rooms are becoming increasingly airtight, meaning that fresh air no longer flows naturally into the rooms. When extracting fumes from hazardous substance cabinets or even when switching on a fume cupboard, negative pressure builds up very quickly. Escape routes are obstructed by doors that are difficult to open. The exhaust air monitoring system for the fume cupboards triggers an alarm.

Solution:

Compact heat recovery with integrated ventilation for schools and large laboratories, with a requirement for 1–3 fume cupboards and/or continuously ventilated hazardous substance cabinets.

The system consists of the following components:

  • Cross-flow heat exchanger made of PE
  • Speed-controlled supply air fan
  • Supply air filter
  • Hot water heating coil
  • Thermostat control valve
  • Filter monitoring by means of differential pressure monitoring, with signal contact
  • Condensate drain
  • Control cabinet with Siemens LOGO control

For up to 7,500 m³/h: Heat exchangers for industrial applications

Heat recovery in schools:

Technical Data:

  • Dimensions: 850x870x1900 mm (W x D x H)
  • Exhaust air connection: 250 mm
  • Fresh air connection: 250 mm
  • Efficiency: > 60%
  • Sound pressure level: < 52 dB(A)
  • Heating capacity: 12 kW, continuously variable
  • Power supply: 1 x 230V/50Hz+N+PE AC
  • Fuse: 1 x B16A with RCD Residual current: 30 mA
  • Cross-section: 3 x 1.5 mm²
  • Air flow rate: 500 m³/h - 1,500 m³/h
  • Pressure drop
    Exhaust air: 350 Pa at 1,500 m³/h,
    270 Pa at 680 m³/h
  • Weight: 67 kg

 

MKW-1500:

Heat exchanger with a capacity of 200–1,500 m3/h. For schools, small and medium-sized industrial facilities or laboratories, in combination with a silencer and ML centrifugal fan.

School Heat Exchanger